| Principle of operation The standards define a voltage transformer as one in which "the  secondary voltage is substantially proportional to the primary voltage and  differs in phase from it by an angle which is approximately zero for an  appropriate direction of the connections."
 This, in essence, means that the voltage transformer has to be as close as  possible to the "ideal" transformer. In an "ideal"  transformer, the secondary voltage vector is exactly opposite and equal to the  primary voltage vector, when multiplied by the turns ratio.
 In a "practical" transformer, errors are introduced because some  current is drawn for the magnetization of the core and because of drops in the  primary and secondary windings due to leakage reactance and winding resistance.  One can thus talk of a voltage error,which is the amount by which the voltage  is less than the applied primary voltage ,and the phase error, which is the  phase angle by which the reversed secondary voltage vector is displaced from  the primary voltage vector.
 Zonal designs its VT's so that the resistance and reactance drops are  minimized. It also uses the best grades of cold rolled grain oriented  electrical steels which enables operation at optimum levels of magnetic  induction, thus reducing both the size and the cost of the VT.
 
 Definitions
 Typical terms used for specifying a voltage transformer (VT)
 
                    Rated primary voltage: This is the rated voltage of the system whose voltage is required to be       stepped down for measurement and protective purposes. Rated secondary voltage: This is the voltage at which the meters and protective devices connected       to the secondary circuit of the voltage transformer operate.Rated burden: This is       the load in terms of volt-amperes (VA) posed by the devices in the       secondary circuit on the VT. This includes the burden imposed by the       connecting leads. The VT is required to be accurate at both the rated       burden and 25% of the rated burden.Accuracy class required: The transformation errors that are permissible, including voltage (ratio)       error and phase angle error. Phase error is specified in minutes. Typical       accuracy classes are Class 0.5, Class 1 and Class 3. Both metering and       protection classes of accuracy are specified. In a metering VT, the VT is       required to be within the specified errors from 80% to 120% of the rated       voltage. In a protection VT, the VT is required to be accurate from 5%       upto the rated voltage factor times the rated voltage.Rated       voltage factor: Depending on the system in which the VT is to be       used, the rated voltage factors to be specified are different. The table       below is adopted from Indian and International standards.  
                    
                      | Rated voltage factor | Rated time | Method of connecting primarywinding in system
 |  
                      | 1.2 | Continuous | Between phases in any networkBetween transformer star-point and earth in any network
 |  
                      | 1.21.5
 | Continuousfor 30 seconds
 | Between phase and earth in an effectively earthed neutral    system |  
                      | 1.21.9
 | Continuousfor 30 seconds
 | Between phase and earth in a non-effectively earthed    neutral system with automatic fault tripping |  
                      | 1.21.9
 | Continuous for 8 hours
 | Between phase and earth in an isolated neutral system without automatic fault tripping or in a resonant earthed
 system without automatic fault tripping
 |  
                    Temperature class of       insulation: The permissible temperature rise over the specified       ambient temperature. Typically, classes E, B and F. Residual       voltage transformer (RVT): RVTs are used for residual earth fault       protection and for discharging capacitor banks. The secondary residual       voltage winding is connected in open delta. Under normal conditions of       operation, there is no voltage output across the residual voltage winding.       When there is an earth fault, a voltage is developed across the open delta       winding which activates the relay. When using a three phase RVT, the       primary neutral should be earthed, as otherwise third harmonic voltages       will appear across the residual winding. 3 phase RVTs typically have 5       limb construction. Metering       Units:11kV metering units consist of one 3 phase VT and 2 CT's       connected together in a single housing. This can be used for three phase       monitoring of energy parameters. It is used with trivector meters and       energy meters.  Standards The Indian and international standard references for VT s are as given in  the table below:
 
                    
                      | Standard
 | Standard Number | Year |  
                      | Indian | IS 3156 | 1992 |  
                      | British | BS 3841 | 1973 |  
                      | British | BS 7625 | 1993 |  
                      | British | BS 7729 | 1994 |  
                      | InternationalElectro technical
 Commission (IEC)
 | IEC 186 | 1987 |  
                      | Australian | AS 1243 | 1982 |  
                      | American | ANSI C.57.13 | 1978 |  Zonal manufactures VT s to all these standards. Our designs are backed up by  extensive type testing at national and international laboratories. 
 Tests
 A number of routine and type tests have to be conducted on VT s before they  can meet the standards specified above. The tests can be classified as:
 
                    Accuracy tests to       determine whether the errors of the VT are within specified limitsDielectric insulation tests such as power frequency withstand voltage test on primary and secondary       windings for one minute, induced over-voltage test , impuse tests with       1.2u/50u wave, and partial discharge tests (for voltage>=6.6 kV) to       determine whether the discharge is below the specified limits. Temperature rise tests Short circuit tests Verification of terminal       markings and polarity  Zonal conducts routine tests on each and every VT produced and all designs  are type tested. Double and triple secondary VT s are also  manufactured.
 Typical specification for a 11 kV VT
 System voltage: 11 kV
 Insulation level voltage (ILV) : 12 /28/75 kV
 Number of phases: Three
 Vector Group: Star / Star
 Ratio: 11 kV/ 110 V
 Burden: 100 VA
 Accuracy: Class 0.5
 Voltage Factor: 1.2 continuous and 1.5 for 30 seconds
 With provision for fuse
 |